Vacuum interrupters

A vacuum interrupter is a switch which uses electrical contacts in a vacuum. It is the core component of medium-voltage and high-voltage circuit-breakers.
Since the arc is contained within the interrupter, switchgear using vacuum interrupters can be very compact compared with switchgear using air, SF6 or oil as the arc-suppression medium. Vacuum interrupters can be used for circuit-breakers (VCB), load break switches (LBS), contactors, rail circuit breakers, etc. Circuit breaker vacuum interrupters are primarily used in the power sector in substation and power-generation facilities, and load-switching vacuum interrupters are used for power grid end users.
We support national and international standards like ANSI/IEEE C37.60, IEC 62271-100, JIS, GB and GOST.

Meidensha vacuum interrupters

Vacuum interrupters for Circuit Breakers

Rated Voltage Rated lightning impulse voltage Power frequency withstand voltage Rated Current Short circuit breaking current with at least 30-40% DC component and Interrupter (Outdiameter-Style)
kV kV kV A 12.5 kA 16 kA 20 kA 25 kA 31.5 kA 40 kA 50 kA
7.2 60 20 630 M20QC
(φ52-A)
800/1250 M30RC
(φ94-A)
1600/2000 M40SC
(φ94-A)
2500/3150 M50TC
(φ110-A)
12/15 75 28 630 M52QC
(φ65-B)
M41QC
(φ69-B)
MA61RC**
(φ94-B)
800/1250 M51RC
(φ82-B)
1600/2000 M71SC
(φ94-B)
M81SC
(φ110-B)
2500/3150 M71TC
(φ110-B)
M81TC
(φ132-B)
MA131TC
(φ150-B)
17.5/24 95/125 38/50 630 M52QC*
(φ65-B)
MA102RC**
(φ94-B)
800/1250 M72RC*
(φ75-B)
M82RC*
(φ75-B)
M102RC
(φ94-B)
1600/2000 M102SC
(φ94-B)
2500 M132TC
(φ120-B)
M203TC
(φ120-C)
36/38 175 80 630 M83QC*
(φ75-B)
M93QC*
(φ94-B)
800/1250 M123QC*
(φ94-B)
1600/2000 M163SC*
(φ110-B)
2500 M203TCB*
(φ120-C)
M253TC*
(φ132-C)
52 250 90 1250/2000 MA285SC*
(φ132-B)
72.5 325 140 1250/2000 MA317SC
(φ132-B)
MA467SC
(φ150-B)
MA507SC
(φ150-B)
* :Additional insulation necessary
** :Capacitor bank switching

Vacuum interrupters for Load Break Switches

Rated Voltage Rated lightning impulse voltage Power frequency withstand voltage Rated Current Short circuit breaking current VI Type
(Dia.-Style)
kV kV kV A kApeak
12/15.5 95 35 630 40 M01QC
(φ60-A)
24/27 125 60 630 40 M02QC
(φ65-B)
36/38 150 70 630 40 M03QC
(φ65-B)

Vacuum interrupters for Auto-Reclosers

Rated Voltage Rated lightning impulse voltage Power frequency withstand voltage Rated Current Short circuit breaking current VI Type
(Dia.-Style)
kV kV kV A kA
15.5/27 110/125 50/60 630 12.5 M52QC*
(φ65-B)
15.5/27 110/125 50/60 800 16 M72QC*
(φ75-B)
38 150 70 630 12.5 M83QC*
(φ75-B)
38 150 70 800 16 M93QC*
(φ82-B)

Vacuum interrupters for Contactor Switches

Rated Voltage Rated lightning impulse voltage Power frequency withstand voltage Rated Current Short circuit breaking current VI Type
(Dia.-Style)
kV kV kV A kA
6.6 45 16 400 4 5G-1
(φ52-A)
6.6 45 16 400 6 7.5G
(φ52-A)

Vacuum interrupters for Mobile Railway applications

Rated Voltage Rated lightning impulse voltage Power frequency withstand voltage Rated Current Short circuit breaking current Short circuit making current VI Type
(Dia.-Style)
kV kV kV A kA kA
18/36 170 70(16.6Hz)
70(50/60Hz)
750(16.6Hz)
450(50/60Hz)
at 18kV
→25(16.6Hz)
at 36kv
→20(50/60Hz)
at 18kA
→62.5(16.6Hz)
163SCM